Compliance: CE certified, and compliant with the Low Voltage Directive 2014/35/EU. Complies with French Technical Recommendation No. 362.
Fire protection: Fire resistance tested to 105 minutes (approved for 90 minutes in accordance with EN 14470-1 and EN 1363-1) and fire-resistant construction certified to EI 180 minutes (type A1, standard NF EN 13501-2).
Thermal insulation: Double thermal insulation with triple walls, panels minimising thermal bridges, and thermally expanding door seals.
Materials and finishes: Steel structure (12/10th external walls) with white epoxy paint (RAL 9010), and melamine-faced interior panels.
Safety and features: Self-closing doors with key lock, ventilation openings (100 mm diameter), and earthing connection point. Door hold-open system with thermoregulated automatic closing at 47°C.
Standardised pictograms in accordance with technical recommendation RT362
Ventilation: Ventilation outlets allowing connection to a ventilation unit (CDV-A).